CO₂, Temperature and Humidity Room Sensor

EE800

EE800 measures accurately CO₂, temperature (T) and relative humidity (RH) in HVAC applications. Additionally, it calculates the dewpoint temperature (Td).

EE800 CO₂ temperature and humidity sensor with display, EU Standard

EE800 CO₂ temperature and humidity sensor, EU Standard

EE800 CO₂ temperature and humidity sensor with display, US Standard

EE800 CO₂ temperature and humidity sensor, US Standard

The E+E dual wavelength NDIR CO₂ sensor compensates for aging effects, is highly insensitive to pollution and offers outstanding long term stability. A multiple point CO₂ and T factory adjustment leads to excellent CO₂ measurement accuracy over the entire T working range.

EE800 with analogue outputs features an optional passive T sensor, while EE800 with digital interface (Modbus RTU or BACnet MS/TP) calculates additional physical quantities: absolute humidity, mixing ratio, enthalpy, frost point temperature and water vapor partial pressure.

Applications

  • Demand controlled ventilation
  • Heating, ventilation and air conditioning
  • Building automation

    Key Features

          • CO₂, T, RH/Td in one room transmitter
          • BACnet, Modbus or analogue outputs
          • Auto-calibration for excellent long term stability
          • Temperature compensation
          • Highly insensitive to pollution
          • Snap-on enclosure for easy installation
          • Optional display
          • Easy user configuration and adjustment

    Technical Data

    Working range CO₂
    0...2000 ppm
    0...5000 ppm
    Accuracy CO₂
    <± (50 ppm +2% of mv)
    <± (50 ppm +3% of mv)
    Working range Temperature
    10...90 % RH
    Accuracy Humidity
    ±3 % RH (30...70 % RH)
    ±5 % (10...90 % RH)
    Working range Temperature
    -20...60 °C (-4...140 °F)
    Accuracy Temperature
    ±0.3 °C (±0.54 °F) voltage output
    ±0.7 °C (±1.26 °F) current output
    Working range Dewpoint
    -30...55 °C (-22...131 °F)
    Accuracy Dewpoint
    < ±2 °C (3.6 °F) for /T/ - /Td/ < 25 °C (45 °F)
    < ±3 °C (5.4 °F) for /T/ - /Td/ < 30 °C (54 °F)
    Output analogue
    0-10 V or 4-20 mA
    Output digital
    Modbus RTU or BACnet MS/TP
    Supply
    24V AC/DC

    FAQ

    Which E+E products are BACnet Certified?

    EE160 and EE210 are tested and certified by BTL (BACnet Testing Laboratories).